Clause-by-clause review of PUE chapter 2.1: open and concealed wiring, conduit and trunking, joints, earthing of metal enclosures, wooden houses.
| Document | PUE 7, Chapter 2.1 Wiring |
| Edition | 2002 (ПУЭ-7, гл. 2.1) |
| Status | Current |
| Issued by | Ministry of Energy of Russia |
| Applies to | Wiring up to 1 kV: open, concealed, in conduit and trunking |
| № | Chapter / section |
|---|---|
| 2.1.1–2.1.15 | Scope, terms |
| 2.1.16–2.1.20 | Selection of wiring type |
| 2.1.21–2.1.30 | Open and concealed wiring |
| 2.1.31–2.1.44 | Conduit and trunking installation |
| 2.1.45–2.1.64 | Joints, branches, earthing |
2.1.1 Applies to power, lighting and secondary circuits up to 1 kV.
2.1.5 Open wiring — on surfaces; concealed — inside structures.
2.1.19 Sections by current, strength and heating; copper from 1.5 mm².
2.1.21–22 Heights: unprotected 2 m, protected/cables 0.5 m.
2.1.23 Concealed in walls — in conduit/chases with protection.
2.1.28 Wall/floor penetrations — in sealed conduit.
2.1.37 All conductors of a circuit in one conduit.
2.1.38 Conduit ID ≥ 1.5 × cable diameter.
2.1.44 Joints only in junction boxes; no welding hidden in walls.
2.1.45 Joints: welding, crimping, soldering, screw/spring terminals.
2.1.52 Metallic conduits — continuous earthing path.
2.1.58–59 Wooden houses: metal conduits or flame-retardant cable (NYM, VVGng).
Chapter 2.1 is the technical basis of any wiring job: sections, conduit sizing 1.5×, joints in boxes (2.1.44), conduit earthing (2.1.52), wooden-house rules (2.1.58–59).
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.