PUE section 1.3: ampacity tables (1.3.4–1.3.7), economic current density, voltage drop check.
| Document | PUE 7, Section 1.3 Conductor selection |
| Edition | 2002 (ПУЭ-7, разд. 1.3) |
| Status | Current |
| Issued by | Ministry of Energy of Russia |
| Applies to | Conductor selection: heating, ampacity (tables 1.3.4–1.3.7), economic density |
| № | Chapter / section |
|---|---|
| 1.3.1–1.3.9 | General, heating |
| 1.3.10–1.3.21 | Ampacity tables |
| 1.3.22–1.3.33 | Economic density, voltage drop |
Conductors must satisfy heating limits: normal, emergency, post-emergency modes.
3-core copper cable in conduit: 1.5 mm² — 14–19 A; 2.5 mm² — 21–27 A; 4 mm² — 28–38 A; 6 mm² — 36–46 A; 10 mm² — 50–70 A. Open — ~20–30% higher. Aluminium — ~25–30% lower. Ambient correction per table 1.3.3.
Copper 2.0–2.5 A/mm² (table 1.3.36); voltage drop check per 1.3.28.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.