IEC 60364-7-710: groups 0/1/2, medical IT systems for group 2, 30 mA RCDs, socket identification, backup supply.
| Document | IEC 60364-7-710 Medical locations |
| Edition | 2018 |
| Status | Current (IEC 60364-7-710) |
| Issued by | IEC |
| Applies to | Medical locations: groups 0/1/2, IT systems for operating theatres, sockets |
| № | Chapter / section |
|---|---|
| 710.30 | Group classification (0, 1, 2) |
| 710.41 | Shock protection |
| 710.5 | Supply and backup |
| 710.6 | Sockets and equipment |
Group 0 — no risk; group 1 — interruption undesirable; group 2 — interruption life-threatening (operating theatres, ICU, delivery).
Group 1: 30 mA RCDs on socket circuits. Group 2: medical IT systems with insulation monitoring; supplementary bonding.
Group 2: two independent sources with automatic transfer; emergency lighting ≥ 50%.
Group 2: ≥ 2 separate socket circuits from different IT systems, identified by marking.