IEC 60364-5-54: electrodes (542), PE sizes (table 54.2), bonding (544), PEN (546).
| Document | IEC 60364-5-54 Earthing and protective conductors |
| Edition | 2011 (в ред. 2022) |
| Status | Current (IEC 60364-5-54) |
| Issued by | IEC |
| Applies to | Earthing arrangements and protective conductors: electrodes, PE sizes, bonding |
| № | Chapter / section |
|---|---|
| 542 | Earth electrodes |
| 543 | Protective conductors |
| 544 | Equipotential bonding |
| 546 | PEN conductors |
Rod, strip, plate, ring, foundation electrodes; TT: RA × Ia ≤ 50 V.
Table 54.2: S ≤ 16 → S; 16 < S ≤ 35 → 16 mm²; S > 35 → S/2. Separate PE: 2.5 mm² protected / 4 mm² unprotected.
Main bonding in every building; supplementary in bathrooms/pools.
Copper ≥ 10 mm² / aluminium ≥ 16 mm²; never broken; not through RCDs; PEN split — PE first.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.