IEC 60364-6:2016: initial verification, insulation 1 MΩ, PE continuity, RCD testing, periodic verification.
| Document | IEC 60364-6 Verification of installations |
| Edition | 2016 |
| Status | Current (IEC 60364-6:2016) |
| Issued by | IEC |
| Applies to | Installation verification: initial, periodic, test scope |
| № | Chapter / section |
|---|---|
| 61 | Initial verification |
| 61.3 | Test scope |
| 62 | Periodic verification |
61.3 Tests: PE continuity; insulation ≥ 1 MΩ (500 V DC) for circuits to 500 V, 0.5 MΩ for SELV; RCD trip ≤ 0.3 s; fault loop impedance; polarity.
Dwellings — every 10 years (UK: 10 years homes, 5 years rentals/commercial); defect categories.