GB 50096-2011 Residential design code, section 8.7 Electrical — translation

Clause-by-clause translation of GB 50096-2011 section 8.7: flat load, RCDs in TN/TT, bathroom local bonding, child-safe sockets, fire RCD up to 500 mA.

🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentGB 50096-2011 Residential design code, section 8.7 Electrical
Edition2011
StatusCurrent (mandatory, GB)
Issued byMOHURD China, in force since 1 August 2012
Applies toResidential building design: flat electrical safety, RCDs, sockets, bonding

Document structure

№Chapter / section
8.7.1Flat design load
8.7.2Safety: RCDs, copper, circuits, bonding
8.7.3Flat intake breaker
8.7.4Child-safe sockets
8.7.5–8.7.6Lighting and socket quantities
GB 50054-2011 Code for design of low-voltage electrical installationsGB 50303-2015 Acceptance of building electrical worksJGJ 16-2008 Electrical design of civil buildingsGB 50096-2011 Residential design code, section 8GB 50057-2010 Building lightning protection codeGB 51348-2019 Civil buildings electrical design standardGB 50168-2018 Cable line installationGB 50052-2009 Supply reliability (China)GB 50058-2014 Explosive atmospheres (China)

8.7.1 Flat load

Load includes lighting, sockets, small appliances with development reserve; power factor 0.9.

8.7.2 Electrical safety

  1. RCDs: TN — wall AC socket circuits may omit RCD; TT — all socket circuits must have RCD;
  2. Copper wiring only; minimum intake sections;
  3. Separate circuits by group (lighting/sockets/kitchen/bathroom);
  4. Main bonding in the building; local bonding in bathrooms (pipes, bath, heating, rebar, socket PE) — junction box even with plastic pipes;
  5. Fire RCD ≤ 500 mA at the intake or distribution branches; alarm to the fire post for large sites;
  6. Automatic disconnection per GB/T 16895.

8.7.3 Flat intake breaker

Main breaker at each flat intake with overcurrent protection.

8.7.4 Child-safe sockets

Sockets at 1.8 m and below must be shutter-protected (child-safe).

8.7.5–8.7.6 Lighting and sockets

Energy-efficient common lighting with automatic control; minimum socket quantities per flat.