Clause-by-clause translation of GB 50057-2010: three protection classes, air-terminal meshes, down conductors, earthing, SPDs.
| Document | GB 50057-2010 Building lightning protection code |
| Edition | 2010 |
| Status | Current (mandatory, GB) |
| Issued by | MOHURD China |
| Applies to | Building lightning protection: classes, air terminals, down conductors, meshes, SPDs |
| № | Chapter / section |
|---|---|
| 1–3 | General, terms, classes |
| 4 | Air terminals and meshes |
| 5 | Down conductors |
| 6 | Lightning earthing |
| 7 | SPDs and bonding |
Class 1 — explosive/high-risk objects; class 2 — large public/production buildings; class 3 — ordinary buildings. Chosen by calculated annual lightning strikes.
Class 1: mesh 5×5 m, down conductors every 12 m; class 2: 10×10 m / 18 m; class 3: 20×20 m / 25 m. Metal roof elements ≥ 0.5 mm usable as natural terminals.
Min 2 per perimeter; steel ≥ 50 mm², copper ≥ 16 mm²; bends ≥ 10×diameter; welded or clamp joints.
Common building earth system preferred; resistance by calculation (typically ≤ 10 Ω combined).
Type 1 (10/350 µs) at the intake for classes 1–2; type 2 (8/20 µs) in main panels; bonding of all incoming services.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.