Clause-by-clause review of PUE-6 (1985) section 1.7: TN-C neutral bonding ("zanulenie"), 4 Ω earth resistance, no RCDs in housing — and how it differs from PUE-7.
| Document | PUE-6 (1985), Section 1.7 Earthing and safety |
| Edition | 1985 (ПУЭ-6) |
| Status | Historical (chapters not replaced by PUE-7 remained until the 2000s) |
| Issued by | Ministry of Energy of the USSR |
| Applies to | Earthing and safety in installations up to 1 kV, 1985 edition |
| № | Chapter / section |
|---|---|
| 1.7.1–1.7.17 | Scope, systems |
| 1.7.18–1.7.33 | Earthing and neutral bonding |
| 1.7.34–1.7.60 | Earthing arrangements |
| 1.7.61–1.7.90 | Protective conductors |
PUE-6 used the old terminology: protective earthing, neutral bonding (zanulenie — TN-C predecessor) and protective disconnection.
1.7.2 Neutral bonding (TN-C) was the standard for LV networks with earthed neutral: PEN served as both neutral and protection.
1.7.5 RCDs only as a supplement in special cases.
1.7.24 Earth resistance ≤ 4 Ω at 380/220 V (10 Ω below 100 kVA) — kept in PUE-7.
1.7.53 Earthing conductors: steel 100 mm² in soil, copper 25 mm², aluminium 35 mm².
PUE-6 legacy is millions of TN-C flats. Modernization: 30 mA RCDs, PEN split in the intake, supplementary bonding in bathrooms (per PUE-7 and SP 256).