NEC Article 517: patient care categories, group 2 IT systems (517.19), essential electrical system (517.30).
| Document | NEC 2023, Article 517 Medical locations |
| Edition | 2023 |
| Status | Current (latest NEC edition) |
| Issued by | NFPA |
| Applies to | US medical locations: groups 1/2, IT systems, essential sources |
| № | Chapter / section |
|---|---|
| 517.2–517.20 | Definitions, categories |
| 517.19 | Group 2 IT systems |
| 517.30–517.40 | Essential sources, emergency lighting |
Patient care areas: categories 1–3; groups 1 (wards) and 2 (operating theatres, ICU).
Group 2 via isolated (IT) systems with insulation monitoring; ≥ 2 identified socket circuits; GFCI except life-support circuits (517.21).
Generator with ≤ 10 s transfer; emergency lighting ≥ 90 minutes.
Automatic single-line diagrams, PUE/GOST/IEC calculations, specification and PDF — from one model.
Start freeData is for reference. Final design decisions must follow current regulations and a qualified engineer.