🇷🇺 PUE — Rules for Electrical Installations (7th ed.)🕰️ PUE-6 — Rules for Electrical Installations (6th ed., 1985)🇺🇸 NEC — National Electrical Code (NFPA 70)🇪🇺 IEC 60364 / HD 60364 (EU national codes)🌎 NOM-001-SEDE, NBR 5410, AEA 90364, RETIE, NCh 4, CNE🇨🇳 GB 50054, GB 50303, JGJ 16, GB/T 16895 (IEC 60364)🇮🇳 IS 732

Document

DocumentIS 732:2019 Electrical Wiring Code (India)
Edition2019
StatusCurrent (India)
Issued byBIS (Bureau of Indian Standards)
Applies toIndian building wiring: installation, protection, earthing, special locations

Document structure

№Chapter / section
3General requirements
5Service requirements
6Wiring
7Protection
8Earthing
9Special locations
10Testing and acceptance
IS 732:2019 Electrical Wiring Code (India)IS 3043:2018 Earthing (India)IS 1293:2019 Plugs and sockets (India)National Electrical Code of India (2011)

Overview

IS 732:2019 — India's main wiring code (BIS). 230/400 V, 50 Hz; IS 1293 sockets (6 A/16 A, three round pins).

Wiring (section 6)

6.3 Minimum copper sections: 1.0 mm² lighting, 1.5 mm² socket circuits. 6.5 Heights: switches 1.2–1.4 m; sockets 0.3–1.0 m.

Protection (section 7)

7.1–7.2 MCBs (IS/IEC 60898) per circuit.

7.4 30 mA RCD mandatory: bathroom/wet-area sockets, outdoor sockets, kitchen appliance sockets; recommended for all dwelling socket circuits. Fire RCD 100–300 mA at the intake.

Earthing (section 8)

TN-S, TN-C-S, TT (IS 3043); earth conductors: copper 4 mm² (open) / 2.5 mm² (conduit); bonding in buildings.

Special locations (section 9)

Bathrooms per IEC 60364-7-701-style zones; sockets via 30 mA RCD; IP44+ luminaires in wet areas.

Testing (section 10)

Insulation test 500 V, ≥ 0.5 MΩ; PE continuity; RCD test button; fault loop impedance; reports.