What is reactive power and cos φ
In AC circuits, power has three components: active P (kW), reactive Q (kVAR), and apparent S (kVA). Power factor cos φ = P / S.
Typical cos φ values:
- Incandescent lamps, heaters: cos φ ≈ 1.0
- LED lights: cos φ ≈ 0.92-0.98
- Induction motors: cos φ ≈ 0.7-0.85
- Welding machines: cos φ ≈ 0.5-0.7
- UPS systems: cos φ ≈ 0.8-0.9
Why low cos φ is bad
- Utility penalties — up to 30% of active energy cost
- Cable overheating — current increases as 1/cos φ
- Oversized cables required
- Voltage drop increases
- Transformer underutilization
Calculation example: 100 kW office
Measured cos φ = 0.75, target cos φ = 0.95.
Qc = P × (tan φ1 — tan φ2) Qc = 100 × (0.882 — 0.329) = 55.3 kVAR
Select automatic capacitor bank 60 kVAR.
Compensator types
- Automatic capacitor banks (3-8 RUB/VAR)
- Active harmonic filters (15-30 RUB/VAR)
- Synchronous compensators (>5 MVAR)
Payback
Penalties: ~$150/month. Cable losses: ~$30/month. CAPEX 60 kVAR bank: ~$2,500. Payback: ~14 months.