UPS: types and selection

Uninterruptible power supplies: offline/line-interactive/online types, power and runtime calculation, batteries, selection for boilers and computers.

Cable cross-sections and ampacityCircuit breaker ratingsElectrical schematic symbols (GOST/IEC)IP protection ratingsRCD types and selectionEarthing systems TN-C, TN-S, TN-C-S, TT, ITWire colour codeBreaker selectivityGenerator selection: petrol or dieselATS and backup powerUPS: types and selectionSolar power plants: types and calculation🌍 World rules

UPS types

TypeTransferOutputApplication
Offline4–10 msMains + stepped sineComputers
Line-interactive2–6 msStabilized mainsServers, boilers
Online (double conversion)0 msPure sine, stabilizedServer rooms, medical, boilers

Power calculation

P(VA) = P(W) / cos φ (0.6–0.7 for computers, 0.8 for boilers). Add 30–50% for inrush currents. Runtime: T = C×U×η/P with η ≈ 0.85.

Rule: run the UPS at 40–70% load.

Selection

TaskRecommendation
Computer / routerLine-interactive 600–1500 VA
Gas boilerOnline 1–3 kVA pure sine + external batteries
Server / NASOnline 1–3 kVA expandable
Whole house (short)Online 5–10 kVA + generator/ATS

Design with GorkyCAD Pro

Automatic single-line diagrams, IEC calculations, specification and PDF — from one model.

Start free

Data is for reference. Final design decisions must follow current regulations and a qualified engineer.